EMS Controller RMC-DR-00
- Category: Microgrid & Industry EMS
- Application: Engergy Monitoring, Load Management, Demand Response, Energy Efficiency Optimization, Renewable Energy Integration, Forecasting and Scheduling
- Benefits: Reduced Energy Costs, Improved Energy Efficiency, Automated Control, Lower Carbon Emissions, Enhanced System Reliability
- Hardwares: Local Controller, Router, Switch, Local Display and Control Terminal
- Software Operation System: Windows, iOS and Android
- Platforms URL: https://cloud.renepoly.com
- Features: Functionalities and Features
- Data Sheet:
EMS Controller RMC-DR-00 Datasheet -
Technical Parameters
| Power Supply | DC 24 V ± 2 V, >6 W + DO load |
| Power Consumption | 24V DC ±2V, basic device operating power consumption is less than 6 W |
| DO Load Capacity | Provided that the external power supply has sufficient capacity, the digital output (DO) interfaces can drive external loads, with a total load capacity of up to 96 W across the 4 DO channels (24 V DC output, maximum current ≤1 A per channel, total current ≤4 A). |
| Communication Protocol (Standard) | Modbus TCP/RTU 、 MQTT |
| Communication Protocol (Licensed / Chargeable options) | 60870‑5‑104 、 DNP3 、 OCPP 、 OPC‑UA |
| RS485 Interface | 6 |
| Ethernet Interface | 2 |
| Digital Inputs | 8, dry‑contact inputs |
| Digital Outputs | 4 |
| Mechinical Relay Outputs | 4 |
| Device System | Linux RT |
| Processor | Quad‑core Arm Cortex‑A7 1.4GHz + RISC‑V E907 600MHz |
| TYPE-C Interface | 1 |
| Dimensions | 128*41*142mm (excluding DIN rail clip) |
| Weight | 700g |
| Operating Temperature | -40°C - 80°C |
| Operating Humidity | 5%-95% |